Online UPS

1KVA – 30KVA


  • Active Power Factor Correction.
  • Single Inverter Card Including Power Device.
  • Communication.
  • Hot Stand By.
  • Customization Available.
  • Scalable Battery.
  • LCD/LED Display.

DES Online UPS

 No. Model  VDC 1/3 Battery Bank
1 1KVA Hi - Frequency 12V 1/1 External
2 2KVA with PFC Charger and Isolation 96V   1/1 External
3 3KVA with PFC Charger and Isolation 96V   1/1 External
4 5KVA with PFC Charger and Isolation 120V   1/1 External
5 7.5KVA with PFC Charger and Isolation 180V   1/1 External
6 10KVA with PFC Charger and Isolation 180V   1/1 External
7 10KVA with PFC Charger and Isolation 360V   3/1 External
8 15KVA with PFC Charger and Isolation 360V   3/1 External
9 15KVA with PFC Charger and Isolation 360V   3/3 External

Technical Specifications

TECHNICAL SPECIFICATION
NXT GEN PFC (Half Electricity Consuming) Series : 1 Phase in-  1 Phase Out
Input Power Rating   1KVA 2 & 3 KVA 5 & 6 KVA 7.5 KVA 10 KVA
Voltage Range V 160 to 280
Frequency Hz 50 +/ - 5%
Input Power Factor   0.9 @ 96VDC,0.82 @180VDC
Charger Topology   Buck- IGBT
  Electrical Connection Input 2.5 Sq mm. 4 Sq mm. 6 Sq mm. 8 Sq mm. 10 Sq mm
Output 1.5 Sq mm. 2.5 Sq mm. 4 & 6 S Q mm. 6 Sq mm. 8 SqMM.
Batt. 96V 4 Sq mm. 8 Sq mm. NA NA NA
120V 4 Sq mm. 6 Sq mm. 16 Sq mm. NA NA
180V 4 Sq mm. 4 Sq mm. 6 Sq mm. 10 Sq mm. 12 Sq mm.
Earth 6 Sq mm. 10 Sq mm.          
Output Power factor Lag 0.8
Voltage V 230
Voltage Regulation % +/- 1
Frequency Hz 50
Frequency Regulation Hz +/- 0.05
Wave Form   Pure Sine wave
Transient Response % <8_10%`90%(Liner Load)
Voltage Harmonic % <3 (Liner Load)
Over Load Capacity   100 to 150 % :18 Sec
150 to 300 % :20 msec
<300 immediately
Crest Factor   3 : 1
Audible Warning Battery Back-up Ending   Intermittent
Over Load   Continuous
Display LED   UPS on # Battery High/ Low # O/P High/Low # Charging ON # Mains Low/ High.
Protection     Output Over Voltage# Output Under Voltage# Over load# Output Short Circuit# Battery Over Voltage# Battery under Voltage, Input Low/ High.
Parameter 7 Segment (up to 7.5KVA)   Output Voltage Meter
LCD Display (10 kva)   Input Voltage & Frequency, Output Voltage & Frequency, Load %, Charging Current, DC Voltage
Interface Db9   Rs 232/USB Port, SNMP (OPTIONAL)
Others Battery Start   Standard
Cabinet wheals   Standard
Extended Battery Charging   Optional
Static By Pass   Optional/ Default Rotary Switch
Overall Efficiency (ac-ac) % >85** (Full Load)
Transfer Time ms 0
Temperature C 0`45
Humidity % 5-95 (non- Condensed)
Dimension Width Inch 10 10 11 13 13
Height Inch 16.5 16.5 21 27 27
Length Inch 22.5 22.5 24 31 31